Factory Automation

Products

Modular I/O



System Module


M-SPE : System Power Extension Module

In a modular IO station, Header module provides system power supply for IO modules. This supply is connected to IO modules through pins and receptacles interface of each module. If number of IO modules attached to Header module increases, system power consumption increases and then the system power supply provided by Header module will not be sufficient. In such case, user needs to add system power supply extension module in the station.

Specification Description
Module Ordering Code M-SPE
System Power Supply Input voltage 24 VDC (11 to 28.8 VDC, ripple included), 12 Watt
Inrush current 20 A for 20 µsec duration
Output voltage 5 VDC
Output current for IO modules 2 A
Protection Reverse polarity protection
Isolation Non-isolated
Field Power Supply Voltage 24 VDC (18 to 30 VDC, ripple included)
Maximum input current at 24 VDC 5 A per input terminal
Current 10 A

M-FPD: Field Power Distribution Module

In a modular IO station, field power distribution module M-FPD provides additional terminals for the field power supply. Module M-FPD provides 8 terminals out of which 4 terminals provide 24 VDC and 4 terminals provide 0 VDC connections. It avoids use of extra terminals in the control panel and facilitates ease of sensor and actuator connections.

Specification Description
Module Ordering Code M-FPD
Field Voltage 24 VDC, 0 VDC
Field power contact Current Max. 10 Amps.

M-FPI: Field Power Isolator Module

In a modular IO station, field power supply is connected to a Header module. This supply is connected to IO modules through pins and receptacles interface of each module. Capacity of pins and receptacles interface of modules is 10A maximum.

Specification Description
Module ordering code M-FPI
Field voltage 5 VDC/ 12 VDC/ 24 VDC/ 48 VDC/ 110 VAC/ 220 VAC
Field power contact current 5 A per input terminal

M-ST: Shield Termination Module

In a modular IO station, shield termination module M-ST provides terminals to connect shield of cables carrying low level signals like analog, communication, etc. So, it is recommended to attach module M-ST after IO module which provides such interfaces e.g. M-UAD2, M-DA2 where analog IOs are connected.

Specification Description
Module ordering code M-ST
Number of shield terminals 8
Contact current at terminal 5 A per input terminal

M-BE: Bus End Module

In a modular IO station, bus end module M-BE provides termination to backplane bus. User should attach bus end module M-BE at the last slot position if there are 16 or more IO modules.

Specification Description
Module Ordering Code M-BE
Terminating Resistor 120 Ω / QW
Power Dissipation Nil

M-B2, M-B3 and M-B5: 2/3/5 Slots Base Module

For Modular IO station with header assembly, assembly modules are mounted on base module. Base module provides 5 Vdc from Power supply module to other modules fixed on it and to IO modules via adapter module.

Item Description
Ordering Code M-B2 M-B3 M-B5
Number of Slots 2 3 5
No. of PSU Slots 1 1 2
No. of Header Slots 1 1 2
No. of ADP Slots No* 1 1
Mounting DIN rail (35 x 7.5 x 1 mm)

M-APSU: Redundant AC Power Supply Module

M-APSU is 110/220 VAC Input Power Supply module which is a Header assembly module. M-APSU module can be mounted in PSU slot of 3-slots base module (M-B3) and 5-slots base module (M-B5). M-APSU module is designed for redundant operation and works on the principle of load sharing with another M-APSU module.

Specification Description
Module Ordering Code M-APSU
Mounting On Base module M-B3 and M-B5
Position on Base Module PSU slot on base module
Input Voltage 100 to 240 VAC (Range from 85 to 264 VAC)
Input Frequency 50/ 60 Hz -6%/ +4%
Maximum Input Apparent Power 90 VA
Inrush Current 20 A, 8 ms or less
Rated Output Voltage 5 VDC; 3.5 A
(2A for IO modules)
Parallel Connection Permitted for redundancy operation with load sharing.
Allowable Momentary Power Failure >20 ms at 220 VAC at full load at an ambient of 55 °C
>10 ms at 110 VAC at full load at an ambient of 55 °C
Protection Output over current 4.4 A or higher
Output short circuit Yes
Input overvoltage Yes
Internal fuse at input side Built-in (Unchangable by user)
Over temperature Yes
Potential Free Contact Output Application ERR contact
Rated switching voltage current 220 VAC/ 24 VDC, 0.5 A
Minimum switching load 1 mA
Response time Off to On 10 ms or less
On to Off 10 ms or less
Life Mechanical 20 million times max. (180 cpm)
Electrical 100,000 times max.
Surge suppressor None
Fuse protection None
Module status indication PW: 1 no., Green LED
LD: 1 no., Amber LED
Withstand voltage (EN 50178) 2300 VAC rms per minute (Between line input terminals and FG terminals and output)
Insulation resistance 100 MΩ or higher by 500 VDC insulation resistance tester
(between line input terminals and FG terminals and output)
Hot swapping Supported.

M-DPSU: 24 VDC Power Supply Module

M-DPSU is 24 VDC Input Power Supply module which is a Header assembly module. M-DPSU module can be fixed in rightmost slot of 2-slots base module (M-B2).

Specification Description
Module Ordering Code M-DPSU
Mounting On Base module M-B2
Position on Base Module PSU slot on base module
Input Voltage 24 VDC (Range from 18 to 30 VDC)
Maximum input power 20 Watts
Inrush current 70 Amps, for 500 micro sec or less
Rated output voltage 5 VDC; 3 A
(2A for IO modules)
Output ripple 20 mV (p – p) maximum
Allowable momentary power failure Less than 10 ms at 24 VDC at full load at an ambient of 55 °C
Protection Output over current Yes. 3.9 Amps or higher
Output short circuit Yes
Input polarity reversal Yes
Input transient Yes
Input overvoltage Yes
Internal fuse at input side Yes. Built-in (Unchangable by user)
Over temperature Supported
Module status indication 1 no., Green LED (PW)
Module status and diagnostics LED indication for local monitoring.
I/O memory consumption Nil
Withstand voltage Between primary and 5VDC terminal 510 VAC per minute;
Insulation resistance Between line input terminals and output) 100 MΩ or higher by 500 VDC insulation resistance tester
Hot swapping Not supported

M-ADP: I/O Adapter Module

M-ADP is I/O Adapter module which is a Header assembly module. M-ADP module can be mounted in ADP slot i.e. the rightmost slot on 3-slots base module (M-B3) and 5-slots base module (M-B5).

Specification Description
Module Ordering Code M-ADP
Mounting On Base module M-B3 and M-B5
Position On Base ADP slot i.e. rightmost slot on base module
LED Indication I/O PW Green LED: 24 VDC field power supply is healthy
Contact Current at Terminal 5 A per input terminal

M-BC: Blank Cover Module

In a modular IO station, blank cover module M-BC has no external connections. User should attach blank cover module M-BC at the last slot position in Header assembly configuration.

Specification Description
Module Ordering Code M-BC
Mounting On base module (M-B5)
LED Indication Not available
Connection Not supported