Factory Automation

Products

Modular I/O



Header Module


CC-Link IE Field Basic: CC-Link IE Field Basic Header Module

Specification Description
Module Ordering Code M-CCB-H
System Power Supply Input voltage 24 VDC (11 to 28.8 VDC, ripple included), 22 Watt
Inrush current 20 A for 20 µsec duration
Protection Reverse polarity protection
Output voltage 5 VDC
Output current for IO modules 2 A
Isolation Non-isolated
Field Power Supply Voltage 24 VDC
Current 10 A
External Connections Network communication RJ45 female
Input power supply
(System power supply and Field power supply)
8 Point terminal block
Configuration port USB 2.0
Fieldbus Support CC-Link IE Field Basic
Station Type Slave station
Number of Occupied Stations 1-4 stations (user configurable)
Number of IO Modules 63 maximum (including system modules)
IO Data Size Depends on number of stations occupied
No. of occupied stations RX RY RWr RWw
1 64 bits 64 bits 32 words 32 words
2 128 bits 128 bits 64 words 64 words
3 192 bits 192 bits 96 words 96 words
4 256 bits 256 bits 128 words 128 words
Cable for Fieldbus Communication Ethernet standard compliant products cable
Cat5e or higher, shielded twisted pair cable
Maximum Cable Distance 100 meters
Network Topology Star

CC-Link IE Field : CC-Link IE Field Header Module

Specification Description
Module Ordering Code M-CCIEF-H
External Connections Network Communication RJ45 female- 2 nos.
Configuration Port USB 2.0
Fieldbus Support CC-Link IE Field
Redundancy Mode Support*3 Non-redundant
Active-Active configuration
Redundant Master
Redundant Line
Maximum Number of Link Points Per Station RX 1K points (1024 points, 128 bytes)
RY 1K points (1024 points, 128 bytes)
RWr 1K points (1024 points, 2K bytes)
RWw 1K points (1024 points, 2K bytes)
Station Type Intelligent device station
Station Number 1 to 120 (settable by rotary switches x16 and x1 (hexadecimal))
Network Number 1 to 239
Communication Speed 1Gbps
Network Topology Line topology, star topology (coexistence of line topology and star topology is also possible), and ring topology
Communication Cable Ethernet cable which satisfies 1000BASE-T standard:
Category 5e or higher, straight cable (double shielded, STP)
Maximum Station-to-Station Distance 100m (conforms to ANSI/TIA/EIA-568-B (Category 5e))
Number of I/O Points
(Local memory)
IX 1K points (1024 points, 128 bytes)
QX 1K points (1024 points, 128 bytes)
IW 1K points (1024 points, 2K bytes)
QW 1K points (1024 points, 2K bytes)
SB 512 points (512 bytes)
Configurable Slots (on base module) Header slot.
Hot Swapping Supported.
Number of IO Modules 63 maximum (including system modules)

CC-Link IE TSN: CC-Link IE TSN Header Module

Specification Description
Module Ordering Code M-CCIEF-H
External Connections Network Communication RJ45 female- 2 nos.
Configuration Port USB 2.0
Fieldbus Support CC-Link IE TSN
Maximum Number of Link Points Per Station RX 1K points (1024 points, 128 bytes)
RY 1K points (1024 points, 128 bytes)
RWr 512 points (512 points, 1K bytes)
RWw 512 points (512 points, 1K bytes)
Station Type Remote station
Communication Speed 1 Gbps
100 Mbps
CC-Link IE TSN Class CC-Link IE TSN Class B, A
CC-Link IE TSN Protocol version Protocol version 2.0
Network Topology Line topology, star topology (coexistence of line topology and star topology is also possible), and ring topology
Communication Cable 1 Gbps - Ethernet cable which satisfies 1000BASE-T standard
Category 5e or higher, straight cable (shielded, STP)
100 Mbps - Ethernet cable which satisfies 100BASE-TX standard
Category 5 or higher, straight cable (shielded, STP)
Maximum Station-to-Station Distance 100m
Number of I/O Points
(Local memory)
IX 1K points (1024 points, 128 bytes)
QX 1K points (1024 points, 128 bytes)
IW 512 points (512 points, 1K bytes)
QW 512 points (512 points, 1K bytes)
SB 512 points (512 bytes)
Configurable Slots (on base module) Header slot.
Number of IO Modules 63 maximum (including system modules)

Modbus TCP: Modbus TCP Header Module

Specification Description
Module Ordering Code M-MT-H
System Power Supply Input voltage 24 VDC (11 to 28.8 VDC, ripple included), 22 Watt
Inrush current 20 A for 20 µsecs duration
Output voltage 5 VDC
Output current for IO modules 2 A
Protection Reverse polarity protection
Isolation Non-isolated
Field Power Supply Voltage 24 VDC (18 to 30 VDC, ripple included)
Current 10 A
External Connections Network communication RJ45 female
Input power supply
(System power supply and Field power supply)
8 Point terminal block
Output System power supply 6-Pins
Output Field power supply 2-Pins
Configuration port USB 2.0
Fieldbus Support Modbus TCP Server; 1 client connection
Baud Rate 10/100 Mbps
IO Data Size Memory type Version 2.0.0.0 and older Version 2.1.0.0 and onwards
IX memory for digital input. 1024 bits (128 bytes)
IW memory for analog input. 256 words 512 words
QX memory for digital output. 1024 bits (128 bytes)
QW memory for analog output. 256 words 512 words
SB memory for status info. 512 bytes
Port Number 502
Cable for Fieldbus Communication Ethernet standard compliant products cable
Category 5 or higher (STP cable)
Maximum Cable Distance 100 meters
Network Topology Star
Number of IO Modules 63 maximum (including system modules )

EtherNet/IP: Ethernet/ IP Header Module

Specification Description
Module Ordering Code M-EIP-H
System Power Supply Input voltage 24 VDC (11 to 28.8 VDC, ripple included), 22 Watt
Inrush current 20 A for 20 µsecs duration
Output voltage 5 VDC
Output current for IO modules 2 A
Protection Reverse polarity protection
Isolation Non-isolated
Field Power Supply Voltage 24 VDC (18 to 30 VDC, ripple included)
Current 10 A
External Connections Network communication RJ45 female- 2 nos. (Configured as embedded switch)
Input power supply
(System and Field power supply)
8 Point terminal block
Output System power supply 6-Pins
Output Field power supply 2-Pins
Configuration port USB 2.0
Fieldbus Support Ethernet/IP™
Ethernet Interfaces 2 (Layer 2 switch with DLR support)
Station Type Communication adapter
DLR Support Yes
IO Data Size Memory type Version 2.0.0.0 and older Version 2.1.0.0 and onwards
IX memory for digital input. 128 bytes
IW memory for analog input. 512 bytes 1152 bytes
QX memory for digital output. 128 bytes
QW memory for analog output. 512 bytes 640 bytes
SB memory for status info. 512 bytes
Physical Layer 10/100BASE-T
Cable for Fieldbus Communication Ethernet standard compliant products cable
Cat5e or higher, shielded twisted pair cable
Maximum Cable Distance 100 meters
Network Topology Line, Tree, Star, Ring
Number of IO Modules 63 maximum (including system modules )

EtherCAT: EtherCAT Header Module

Specification Description
Module Ordering Code M-ECAT-H
System Power Supply Input voltage 24 VDC (11 to 28.8 VDC, ripple included), 22 Watt
Inrush current 20 A for 20 µsecs duration
Output voltage 5 VDC
Output current for IO modules 2 A
Protection Reverse polarity protection
Isolation Non-isolated
Field Power Supply Voltage 24 VDC
Current 10 A
External Connections Network communication RJ45 female- 2 nos.
Input power supply
(System and Field power supply)
8 Point terminal block
Output System power supply 6-Pins
Output Field power supply 2-Pins
Configuration port USB 2.0, Micro USB B type connector
Fieldbus Support EtherCAT
Ethernet Interfaces 2
Station Type EtherCAT Slave
Cyclic communication Process data Object
Mailbox communication CoE ( for SDO request, SDO response, SDO information, diagnostics data, emergency messages), EoE
Minimum IO cycle time 1 ms
IO Data Size Memory type
IX memory for digital input. 128 bytes
IW memory for analog input. 1024 bytes
QX memory for digital output. 128 bytes
QW memory for analog output. 1024 bytes
SB memory for status info. 512 bytes
Physical Layer 10/100BASE-T
Cable for Fieldbus Communication Ethernet standard compliant products cable
Cat5e or higher, shielded twisted pair cable
Maximum Cable Distance 100 meters
Network Topology Line, Tree, Star, Ring
Number of IO Modules 63 maximum (including system modules)